Voltage Unbalance Factor (VUF)
The Voltage Unbalance Factor (VUF) is a quantitative index used to describe the degree of asymmetry in a three-phase power system.

Definition of Phase Imbalance
Phase imbalance (also called unbalance) in a three-phase AC system occurs when the three phase voltages or currents are not equal in magnitude and/or not separated by exactly \(120^\circ\). For an ideally balanced system,
\[
|V_a| = |V_b| = |V_c|,\qquad
\angle V_a – \angle V_b = \angle V_b – \angle V_c = 120^\circ.
\]
Any deviation from these relations constitutes imbalance and introduces negative-sequence components that heat machines, increase losses, and degrade power quality.
Quantifying Imbalance
(a) Symmetrical-components index (Voltage Unbalance Factor, VUF)
Decompose the phase voltages into positive-sequence \(V_{1}\) and negative-sequence \(V_{2}\).
The Voltage Unbalance Factor is
\[
\mathrm{VUF} = \frac{|V_{2}|}{|V_{1}|}\times 100\%.
\]
Likewise, the current counterpart is
\[
\mathrm{IUF} = \frac{|I_{2}|}{|I_{1}|}\times 100\%.
\]
(b) Practical three-reading method (Percent voltage unbalance)
Measure the three line-to-line (or line-to-neutral) RMS voltages \(V_1,V_2,V_3\). Let
\(\overline{V}=(V_1+V_2+V_3)/3\) and \(\Delta V=\max(|V_1-\overline{V}|,|V_2-\overline{V}|,|V_3-\overline{V}|)\).
Then the percent unbalance is
\[
\%\text{ Unbalance} = \frac{\Delta V}{\overline{V}}\times 100\%.
\]
increase as imbalance worsens. Use the one your standard or test plan requires.
Examples of Phase Imbalance
- Unequal magnitudes. L-L voltages read 400 V, 392 V, 408 V. The average is \(\overline{V}=400\) and
\(\Delta V=8\Rightarrow \%\text{Unbalance}=2\%\). - Unequal phase angles. Magnitudes are equal, but phase displacements are \(118^\circ\), \(122^\circ\), and \(120^\circ\);
negative-sequence components appear even with equal RMS values. - Unequal currents. A feeder carries \(I_a=60\) A, \(I_b=45\) A, \(I_c=50\) A due to uneven single-phase loading.
- Single-phasing. One conductor opens; motors attempt to run on two phases and rapidly overheat.