Harmonic Injection
Harmonic Injection is a deliberate introduction of harmonic components into an AC power system which is testing method usually used for validation and research purposes with the support of programmable AC power supply.

Definition of Harmonic Injection
Harmonic injection is the intentional superposition of specified harmonic components (voltage or current) onto a fundamental AC waveform, typically for power-quality testing, product validation, or research. In power systems, harmonics are sinusoidal components whose frequencies are integer multiples of the fundamental frequency \(f\) (e.g., 50 Hz or 60 Hz).
Frequency examples (50 Hz system): 2nd: 100 Hz, 3rd: 150 Hz, 5th: 250 Hz, 7th: 350 Hz, …
Note: Components at non-integer multiples of \(f\) are usually called interharmonics. They can also be injected for testing, but strictly speaking they are not “harmonics.”

Mathematical Modeling
A harmonic-injected voltage can be represented in Fourier series form as:
\[
v(t) = V_1 \sin(\omega t + \phi_1) + \sum_{n=2}^{N} V_n \sin(n\omega t + \phi_n)
\]
- \(V_1\): fundamental amplitude (state RMS or peak consistently)
- \(V_n\): amplitude of the \(n\)-th harmonic (same basis as \(V_1\))
- \(\phi_n\): phase of the \(n\)-th harmonic, typically referenced to the fundamental
- \(f\): fundamental frequency; \(\omega = 2\pi f\)
Engineering note: “\(x\%\) of the \(n\)-th harmonic” often means \(V_n = x\% \cdot V_1\) in RMS terms, but some instruments define harmonic magnitudes in peak/phasor form. Always state the magnitude basis and reference.
Example: Injecting 3rd and 5th Harmonics
Assume a per-unit model with \(V_1 = 1.0\,\text{pu}\) and zero phase shifts \((\phi_1=\phi_3=\phi_5=0)\). Let \(V_3 = 0.05\,\text{pu}\) (5% 3rd harmonic) and \(V_5 = 0.02\,\text{pu}\) (2% 5th harmonic). Then:
\[
v(t) = \sin(\omega t) + 0.05 \sin(3\omega t) + 0.02 \sin(5\omega t)
\]
50 Hz mapping: 3rd \(\rightarrow\) 150 Hz, 5th \(\rightarrow\) 250 Hz. (60 Hz mapping: 3rd \(\rightarrow\) 180 Hz, 5th \(\rightarrow\) 300 Hz.)
Three-Phase Note: Triplen Harmonics and Neutral Summation
In three-phase systems, triplen harmonics are orders \(n = 3, 9, 15, \dots\) (i.e., \(n=3k\)). For a balanced three-phase fundamental, phase quantities are separated by \(120^\circ\). For the \(n\)-th harmonic, the phase shift becomes \(n \times 120^\circ\). When \(n=3k\):
\[
n \cdot 120^\circ = 3k \cdot 120^\circ = 360^\circ k
\]
This implies the triplen harmonic components in all three phases are effectively in phase. In a 4-wire system with a neutral conductor, these in-phase triplen harmonic currents can add in the neutral rather than cancel, increasing neutral current and heating risk.
Test-design takeaway: When injecting 3rd/9th/15th harmonics in three-phase setups, explicitly consider 3-wire vs 4-wire wiring, neutral conductor rating, and DUT neutral-related constraints. Bear in mind that the capability of generate harmonic from user-defined interface is a critical feature for a grid-compatibility testing equipment; check our TITAN Series Regenerative Grid Simulator for related technical information.
Voltage Harmonic Injection vs Current Harmonic Injection
Voltage harmonic injection
- Controlled variable: the source voltage waveform applied to the DUT
- Primary question: how the DUT behaves under a distorted grid voltage
- What you observe: harmonic currents depend on DUT input impedance and control behavior
- Typical risks: overcurrent/overheating if the DUT draws disproportionate harmonic currents at certain orders
Current harmonic injection
- Controlled variable: the current waveform drawn from or driven into a network (e.g., via active load/current source)
- Primary question: what harmonic spectrum a load imposes and what it does to the upstream supply/network
- What you observe: resulting voltage distortion depends on source impedance and network strength
- Typical risks: unexpected voltage distortion/instability if the source is weak or control loops interact
Rule of thumb:
If the test question is “How does the DUT behave under a distorted grid voltage?” use voltage injection. If the test question is “What harmonic current spectrum is imposed on the network, and what is the upstream impact?” use current injection.
Practical Implementation Notes
- Magnitude basis: specify RMS vs peak and whether referenced to \(V_1/I_1\) or absolute.
- Phase reference: define the phase convention (sine vs cosine reference, and the reference phasor).
- Order list: state the injected harmonic orders, limits, and whether triplen orders are included for 3-phase tests.
- Headroom: verify instrument voltage/current/apparent-power headroom; harmonics can raise RMS and peak values.
Useful Tools of Harmonic-Related Calculation and Engineering
Generative distorted AC waveform with arbitrary settings of individual harmonics by orders, Vrms and phase shifts. The total harmonic distortion calculator development by ActionPower facilitates your spectral analysis of harmonics in three-phase power system.