Home Contact EN

Blogs & Insights

Find out the latest innovations from ActionPower

Published on: Updated on: Author: Zhiwei Bao Reviewed: Sen Wang

Interharmonics in Electrical Power Systems: Causes, Impacts, and Testing Emulations




Inter-harmonics are not the same as harmonics though both of them lead to issues among electrical power system. While the effects of harmonics on distribution system and end-use devices have acquired relatively more attention and thoroughly studied by researchers and engineers, inter-harmonics are usually neglected yet they have more profound impacts and repercussion due to the nature that their frequency is not of integer multiple of that of fundamental frequency.

Modern electrical power systems rely on bunches of advanced equipment and devices, among others and more specifically, grid-tied power conversion system, PV inverters and even until the tiny and yet essential SMPS within industrial equipment such as server PSU and consumer appliances. However, their nature of non-linear loads and the very switching mechanisms that make these devices efficient and indispensable also give rise to inter-harmonics components, while they remain essential to the reliable operation of today’s power systems.

understand inter-harmonics

Technical Fundamentals to Inter-Harmonics: Definitions, Causes and Effects

Inter-harmonics are frequency components in a power system whose frequencies are not integer multiples of the fundamental frequency, for example, a 50 Hz component superimposed to a 60Hz fundamental.

Standard and Fundamental Waveform Component with Fixed Frequency and RMS

Supposing a fundamental component that follows a sinusoidal waveform pattern which is typical and ideal for a common power systems:

$$v(t) = V_m \sin(2\pi f_0 t)  \qquad(1) $$

where

  • \(v(t)\) stands for instantaneous voltage as a function of time
  • \(V_m\) represents peak amplitude of the fundamental component
  • \(f_0\) is the fundamental frequency (typically 50 Hz or 60 Hz)
  • \(t\) stands for time

In this case, usually where \(f_0 = 50\ \text{Hz}\) or \(60\ \text{Hz}\), the waveform follows a fixed frequency and with a stable RMS (root-mean square) voltage or current value.

fundamental 60hz waveform

Superimpose Non-Integer Multiple Frequency Over the Fundamental Waveform & Modulation Effect

Assuming that an additional frequency component, here defined as noninteger harmonics, is laid over to the fundamental waveform of 60Hz frequency, which can be expressed by formula as below:

$$v(t) = V_m \sin(2\pi \cdot 60t) + 0.02 \cdot V_m \sin(2\pi \cdot 50t)\qquad(2)$$

where

  • the first term represents 60 Hz fundamental component
  • the second term stands for a 50 Hz component with an amplitude equal to 2% of the fundamental
  • and since 50 Hz is not an integer multiple of 60 Hz, it is classified as an inter-harmonic

Alternatively, if without specified frequency for either the fundamental waveform or the additional components, the formula can be written as:

$$v(t) = V_1 \sin(2\pi f_1 t) + V_2 \sin(2\pi f_2 t)\qquad(3)$$

in which,

  • \(V_1\) is the amplitude of the fundamental (e.g., nominal 120 V RMS → peak ~170 V)
  • \(V_2\) is the amplitude of the inter-harmonic (here 2% of \(V_1\))
  • \(f_1\) stands for the fundamental frequency (60 Hz)
  • \(f_2\) stands for inter-harmonic frequency (50 Hz)

Superimposed waveform with interharmonics with 2% amplitude

On the basis of trigonometric expansion, \( \sin A + \sin B = 2 \sin\!\left(\tfrac{A+B}{2}\right) \cos\!\left(\tfrac{A-B}{2}\right) \), the formula (3) can be rewritten approximately into the below equation supposing that \(V_2\ll V_1\):

$$ \begin{aligned} v(t) &= \frac{V_1+V_2}{2}\,\Bigl[\sin\!\bigl(2\pi f_1 t\bigr)+\sin\!\bigl(2\pi f_2 t\bigr)\Bigr] \;+\; \frac{V_1-V_2}{2}\,\Bigl[\sin\!\bigl(2\pi f_1 t\bigr)-\sin\!\bigl(2\pi f_2 t\bigr)\Bigr] \\[4pt] &= (V_1+V_2)\,\sin\!\Bigl(2\pi \tfrac{f_1+f_2}{2}\,t\Bigr)\,\cos\!\Bigl(2\pi \tfrac{f_1-f_2}{2}\,t\Bigr) \\ &\quad + (V_1-V_2)\,\cos\!\Bigl(2\pi \tfrac{f_1+f_2}{2}\,t\Bigr)\,\sin\!\Bigl(2\pi \tfrac{f_1-f_2}{2}\,t\Bigr)\qquad (4) \end{aligned} $$

Superimposed waveform with interharmonics with 2% amplitude and envelope

This decomposition shows a carrier at the average frequency

$$
f_{\mathrm{car}} = \tfrac{f_1+f_2}{2},
$$

whose amplitude/phase is modulated by a low-frequency envelope at

$$
f_{\mathrm{mod}} = \lvert f_1 – f_2 \rvert .
$$

For the numerical example in (2):

$$
f_{\mathrm{car}} = 55\ \text{Hz}, \qquad f_{\mathrm{mod}} = 10\ \text{Hz}.
$$

RMS Fluctuation Caused by Inter-Harmonics

When the fundamental and an inter-harmonic component are superimposed, the resulting waveform no longer maintains a fixed RMS value. Instead, the effective voltage oscillates at the modulation frequency \(f_{\mathrm{mod}}\).

The instantaneous RMS, defined over one fundamental period \(T_0 = 1/f_1\), can be expressed as:

$$
\mathrm{RMS}(t) = \sqrt{\frac{1}{T_0}\int_{t}^{t+T_0} v^2(\tau)\, d\tau},
\qquad T_0 = \frac{1}{f_1}
\qquad (5)
$$

For the composite signal of equation (3):

$$
v(t) = V_1 \sin(2\pi f_1 t) + V_2 \sin(2\pi f_2 t),
$$

the squared term \(v^2(t)\) contains a cross term proportional to \(\cos\!\bigl(2\pi(f_1 – f_2)t\bigr)\), which introduces a low-frequency variation in the RMS value. Assuming \(V_2 \ll V_1\), the RMS can be approximated by:

$$
\mathrm{RMS}(t) \;\approx\; V_{1,\mathrm{RMS}}
\;+\; \Delta V \cos\!\left(2\pi f_{\mathrm{mod}} t + \phi\right)
\qquad (6)
$$

where:

  • \(V_{1,\mathrm{RMS}} = \tfrac{V_1}{\sqrt{2}}\) is the RMS of the fundamental,
  • \(\Delta V\) is the fluctuation amplitude introduced by the inter-harmonic (proportional to \(V_2\)),
  • \(f_{\mathrm{mod}} = |f_1 – f_2|\) is the modulation frequency.

Thus, in the case of equation (2), the RMS oscillates around its nominal value of \(120\ \text{V}\) at a frequency of \(10\ \text{Hz}\), with a fluctuation amplitude determined by the 2% inter-harmonic component.

RMS value in short time

Impacts of Inter-Harmonics on Devices and Electrical Power Systems

Some results caused inter-harmonics are similar to those by harmonics, however, more complex issued and undesired impacts might be spotted due to the unique features of inter-harmonics including its non-periodic nature, RMS fluctuation and modulation frequency. Generally, the impacts can be categorized into three broad types including overloads, oscillations, and distortions. [1]

Overloads

Inter-harmonics contribute to additional energy losses in the system, which manifest as extra heating in conductors and transformers. They may also overload passive filters or cause saturation in current transformers. A wide range of inter-harmonic frequencies increases the risk of resonance, which can amplify these overload effects and accelerate equipment ageing.

Oscillation and Acoustic Disturbances

Mechanical resonances is one of the probably problems when the frequency of inter-harmonics matches that of rotating machines or motor drives and subsequently give rise to oscillatory toques and vibrations. Apart from mechanical issues, personnel surrounding the equipment may also witness audible acoustic disturbances due to overlaid frequencies.

When this issue occurs in scenarios of telecommunications, the overlapped frequency of inter-harmonics will result in interference with the communication signals.

Distortion of the Fundamental Waveform

Waveform distortion refers to the distorted sinusoidal shape of the fundamental, which precision electronic devices that depends on precise zero-crossing detection or on stable crest voltage may see their operation impaired and disrupted from normal performance.

Flicker and Power-Line Communication Interferences

Light system suffers from more perceptible impacts when inter-harmonics happen in its electrical system, which are referred to as light flickers, as a consequence of the fluctuated RMS voltage. The reason for which these flickers are visually perceptible are that many inter-harmonic components whose modulation frequencies are overlapped with the fundamental, may coincidentally match human’s visual sensitivity which lies between about 0.5 Hz and 30 Hz.

Inter-harmonics above 120 Hz tend to have little influence on flicker, but those below this threshold can have a strong visual impact.

Power-line communication (PLC) systems are both a source of and susceptible to inter-harmonics [2]. Many PLC and ripple-control signals use single inter-harmonic frequencies, while modern two-way smart meters rely on step changes in voltage or current that contain multiple inter-harmonic components. If inter-harmonics from other sources overlap in frequency and magnitude, they can interfere with communication reliability. For example, inter-harmonics generated by VSC-HVDC converters have been shown to disturb automatic meter reading systems. Attempts to strengthen PLC signals to overcome such interference are limited, since increasing their magnitude may itself introduce visible flicker.

Grid Emulators Help with Replicating Inter-Harmonics of Reliability and Adaptability Validation

No power systems are perfect and would supply a clean profile of AC power due to the existence of miscellaneous devices and equipment which are in nature non-linear loads that will generate not only harmonics but also inter-harmonics that in turn distort the fundamental AC power. Yet as all these devices and equipment are supposed to work desirably stable and efficiently, they must withstand the distortions and impacts caused by inter-harmonics.

Grid emulators offers a platform with which engineers and R+D personnel can replicate these conditions actively and artificially instead of testing devices by connecting them to a real AC electrical system where the occurrence of intern-harmonics is random and uncontrollable.

How ActionPower’s Grid Simulator Support Your Testing with Inter-Harmonics Replication?

ActionPower’s range of programmable AC power supplies and regenerative high-power grid simulator are designed precisely for purposes of meeting testing requirements in laboratory and production line. Alternatively, find more technical details about how grid simulation power testing faciliates harmonic immunity validation.

Our systems are highlighted by their flexiblity with user-defined and controllable harmonics and internarmonic components generation as well as independent phase control, wide frequency bandwidth to repeatably executing testing cases and applications against the DUTs including PV inverters, EV chargers, SMPS units, and other power electronic devices can be validated against the real-world disturbances of modern grids.

Generative distorted AC waveform with arbitrary settings of individual harmonics by orders, Vrms and phase shifts. The total harmonic distortion calculator development by ActionPower facilitates your spectral analysis of harmonics in three-phase power system.

Open THD Calculator

Bibliography

  • [1] Understanding Power System Interharmonics, Michael B. Marz March 29, 2017, Link
  • [2] Error Analysis of Narrowband Power-Line Communication in the Off-Grid Electrical System, Sensors 2022, 22(6), 2265, Link

 

 

 


ActionPower research and development team

Talk to ActionPower

From ActionPower we are open to listening to your suggestions and opinions.

For further media contact or consultation about any topics which might be of your interest about our company, you will be welcomed to send us an email to:

info@actionpowertest.com

Latest News


PRL DC Load Simulator Introduced by ActionPower for AI Server Workload Validation

Dynamics and power regeneration are no longer compromise to each other. Adopting innovation topology technologies is the PRL DC Load Simulator that accommodates ultra-fast dynamics, regenerative load and high-power scalability from a united single system.



ActionPower to Debut MIX Series Hybrid Power Supply at Europe Automotive Testing Expo 2025

The latest hybrid programmable power supply by ActionPower comes with 6 channels hybrid interface and allows AC/DC module arbitrary combination for flexible testing configuration where both AC and DC are...



CONTANCT US

Zhiwei Bao, SEO Engineer and technical copywriter at ActionPower
About the Author

Zhiwei Bao

Industrial Automation Power Electronics Product Marketing Field Application

Zhiwei Bao holds 20+ patents in the field of mechanical engineering and is keen on industrial automation and product marketing. His interdisciplinary background, along with his passion and initiative for learning, has led him to a profound understanding of power electronics. He manages the technical copywriting for programmable power and testing topics at ActionPower through product-marketing-driven approaches.

About Zhiwei Bao

Explore More

diesel generator and data center for AI facility

The Surge in AI data Center Construction is the Boom in Industrial...

Figures of Soaring AI Data Center Construction Following AI Boom Public available data shows the investment to data center construction...



Why Linear Loads Demonstrates Better Dynamics Performance than Regenerative Ones? And How ActionPower Breaks the Boundary?

Why Linear Loads Demonstrates Better Dynamics Performance than Regenerative Ones? And How...

Conventional testing applications where programmable electronic loads are deployed used to see a definite trade-off between dynamic performance and the...



combination of software and hardware is battery cycler's key feature

Grid Code Compliance Test Explained: What to Validate and Which Standards to...

Facing the modern grid landscape is the ever more important grid interconnection and interoperability, since DERs are now enacting as...




Get in Contact

Global Contact

Sales Network & Locations

If you are looking for an automated test system to validate your products during development and research stages to make sure of their successful commercial launch, ACTIONPOWER will be at your disposal to study your specifications and requirements to provided either standard or customized testing solutions.

Product Inquiry

Specification-matching testing and simulation solutions need discussion of both parties. Actionpower welcomes you inquirt to study together with us about how we can automate your testing processes.

Send Inquiry

Trade Shows & Events

These are the upcoming events and places you can find ACTIONPOWER and talk with us face-to-face!

Check Events

Social Media

Follow us to keep updated of our innovations.

LinkedInTwitter
Quick Model Access

Smart Discovery

Access our Power Supply Wizard to find the right programmable power supply for your use cases and testing scenarios.

discover programmable power supply by filtering with current, voltage and power ranges
CONTACT US

Contact Us

Professionalism is what we care about. Why not email us with your technical requirements fully explained rather than submitting a simple message so that we revert more proactively with detailed solutions?

Subscribe to Newsletter

Thank you for subscribing!