Inter-harmonics are not the same as harmonics though both of them lead to issues among electrical power system. While the effects of harmonics on distribution system and end-use devices have acquired relatively more attention and thoroughly studied by researchers and engineers, inter-harmonics are usually neglected yet they have more profound impacts and repercussion due to the nature that their frequency is not of integer multiple of that of fundamental frequency.
Modern electrical power systems rely on bunches of advanced equipment and devices, among others and more specifically, grid-tied power conversion system, PV inverters and even until the tiny and yet essential SMPS within industrial equipment such as server PSU and consumer appliances. However, their nature of non-linear loads and the very switching mechanisms that make these devices efficient and indispensable also give rise to inter-harmonics components, while they remain essential to the reliable operation of today’s power systems.

Inter-harmonics are frequency components in a power system whose frequencies are not integer multiples of the fundamental frequency, for example, a 50 Hz component superimposed to a 60Hz fundamental.
Supposing a fundamental component that follows a sinusoidal waveform pattern which is typical and ideal for a common power systems:
where
In this case, usually where \(f_0 = 50\ \text{Hz}\) or \(60\ \text{Hz}\), the waveform follows a fixed frequency and with a stable RMS (root-mean square) voltage or current value.

Assuming that an additional frequency component, here defined as noninteger harmonics, is laid over to the fundamental waveform of 60Hz frequency, which can be expressed by formula as below:
where
Alternatively, if without specified frequency for either the fundamental waveform or the additional components, the formula can be written as:
in which,

On the basis of trigonometric expansion, \( \sin A + \sin B = 2 \sin\!\left(\tfrac{A+B}{2}\right) \cos\!\left(\tfrac{A-B}{2}\right) \), the formula (3) can be rewritten approximately into the below equation supposing that \(V_2\ll V_1\):

This decomposition shows a carrier at the average frequency
whose amplitude/phase is modulated by a low-frequency envelope at
For the numerical example in (2):
When the fundamental and an inter-harmonic component are superimposed, the resulting waveform no longer maintains a fixed RMS value. Instead, the effective voltage oscillates at the modulation frequency \(f_{\mathrm{mod}}\).
The instantaneous RMS, defined over one fundamental period \(T_0 = 1/f_1\), can be expressed as:
For the composite signal of equation (3):
the squared term \(v^2(t)\) contains a cross term proportional to \(\cos\!\bigl(2\pi(f_1 – f_2)t\bigr)\), which introduces a low-frequency variation in the RMS value. Assuming \(V_2 \ll V_1\), the RMS can be approximated by:
where:
Thus, in the case of equation (2), the RMS oscillates around its nominal value of \(120\ \text{V}\) at a frequency of \(10\ \text{Hz}\), with a fluctuation amplitude determined by the 2% inter-harmonic component.

Some results caused inter-harmonics are similar to those by harmonics, however, more complex issued and undesired impacts might be spotted due to the unique features of inter-harmonics including its non-periodic nature, RMS fluctuation and modulation frequency. Generally, the impacts can be categorized into three broad types including overloads, oscillations, and distortions. [1]
Inter-harmonics contribute to additional energy losses in the system, which manifest as extra heating in conductors and transformers. They may also overload passive filters or cause saturation in current transformers. A wide range of inter-harmonic frequencies increases the risk of resonance, which can amplify these overload effects and accelerate equipment ageing.
Mechanical resonances is one of the probably problems when the frequency of inter-harmonics matches that of rotating machines or motor drives and subsequently give rise to oscillatory toques and vibrations. Apart from mechanical issues, personnel surrounding the equipment may also witness audible acoustic disturbances due to overlaid frequencies.
When this issue occurs in scenarios of telecommunications, the overlapped frequency of inter-harmonics will result in interference with the communication signals.
Waveform distortion refers to the distorted sinusoidal shape of the fundamental, which precision electronic devices that depends on precise zero-crossing detection or on stable crest voltage may see their operation impaired and disrupted from normal performance.
Light system suffers from more perceptible impacts when inter-harmonics happen in its electrical system, which are referred to as light flickers, as a consequence of the fluctuated RMS voltage. The reason for which these flickers are visually perceptible are that many inter-harmonic components whose modulation frequencies are overlapped with the fundamental, may coincidentally match human’s visual sensitivity which lies between about 0.5 Hz and 30 Hz.
Inter-harmonics above 120 Hz tend to have little influence on flicker, but those below this threshold can have a strong visual impact.
Power-line communication (PLC) systems are both a source of and susceptible to inter-harmonics [2]. Many PLC and ripple-control signals use single inter-harmonic frequencies, while modern two-way smart meters rely on step changes in voltage or current that contain multiple inter-harmonic components. If inter-harmonics from other sources overlap in frequency and magnitude, they can interfere with communication reliability. For example, inter-harmonics generated by VSC-HVDC converters have been shown to disturb automatic meter reading systems. Attempts to strengthen PLC signals to overcome such interference are limited, since increasing their magnitude may itself introduce visible flicker.
No power systems are perfect and would supply a clean profile of AC power due to the existence of miscellaneous devices and equipment which are in nature non-linear loads that will generate not only harmonics but also inter-harmonics that in turn distort the fundamental AC power. Yet as all these devices and equipment are supposed to work desirably stable and efficiently, they must withstand the distortions and impacts caused by inter-harmonics.
Grid emulators offers a platform with which engineers and R+D personnel can replicate these conditions actively and artificially instead of testing devices by connecting them to a real AC electrical system where the occurrence of intern-harmonics is random and uncontrollable.
ActionPower’s range of programmable AC power supplies and regenerative high-power grid simulator are designed precisely for purposes of meeting testing requirements in laboratory and production line. Alternatively, find more technical details about how grid simulation power testing faciliates harmonic immunity validation.
Our systems are highlighted by their flexiblity with user-defined and controllable harmonics and internarmonic components generation as well as independent phase control, wide frequency bandwidth to repeatably executing testing cases and applications against the DUTs including PV inverters, EV chargers, SMPS units, and other power electronic devices can be validated against the real-world disturbances of modern grids.
Generative distorted AC waveform with arbitrary settings of individual harmonics by orders, Vrms and phase shifts. The total harmonic distortion calculator development by ActionPower facilitates your spectral analysis of harmonics in three-phase power system.

Zhiwei Bao holds 20+ patents in the field of mechanical engineering and is keen on industrial automation and product marketing. His interdisciplinary background, along with his passion and initiative for learning, has led him to a profound understanding of power electronics. He manages the technical copywriting for programmable power and testing topics at ActionPower through product-marketing-driven approaches.
About Zhiwei Bao
If you are looking for an automated test system to validate your products during development and research stages to make sure of their successful commercial launch, ACTIONPOWER will be at your disposal to study your specifications and requirements to provided either standard or customized testing solutions.
Specification-matching testing and simulation solutions need discussion of both parties. Actionpower welcomes you inquirt to study together with us about how we can automate your testing processes.
Send InquiryThese are the upcoming events and places you can find ACTIONPOWER and talk with us face-to-face!
Check EventsProfessionalism is what we care about. Why not email us with your technical requirements fully explained rather than submitting a simple message so that we revert more proactively with detailed solutions?