Harmonics in Electrical Power Systems: Technical Explanations and Power Testing Solutions




Harmonics has not been any kind of new issue to 3-phase AC power systems which are typically designed to operate at frequencies of 50 or 60 Hz [1].

As early as back to 1910s when Sheinmetz [2] who was the one of the first engineers called attention to the study of harmonics in three-phase power systems proposed the delta connexions for blocking third harmonic currents, efforts have been continuously attached to mitigating and solving the impacts of harmonics in affecting power qualities and how electrical devices ideally operate as they are supposed to.

This article aims to explain the origins and types of harmonics as well as its effect on power systems for you to acquire essential understanding of such kind of omnipresent electrical phenomenon that has accompanied all alone with the development and power electronics.

delta connections - Schematic of a Delta-connected load in a three-phase system. Three impedance components form a closed triangle with nodes labeled a, b, and c. Line currents Ia, Ib, and Ic flow into the junctions, while phase currents Iab, Ibc, and Ica circulate through the branches with designated directional arrows. A line-to-line voltage Vab with polarity markers is shown across the bottom branch.

ActionPower’s versatile grid simulators are capable of emulating a wide range of harmonics and injecting them into DUT’s power circuit to verify its stability and reliability against grid anomalies and power quality issues in accordance with applicable standards. To discover further information, visit our page of grid emulation solutions.

Generative distorted AC waveform with arbitrary settings of individual harmonics by orders, Vrms and phase shifts. The total harmonic distortion calculator development by ActionPower facilitates your spectral analysis of harmonics in three-phase power system.

Open THD Calculator

 


What are Harmonics?

In an alternating current power system, the voltage and current waveforms typically follow a sinewave shape which can be simply defined by \( v(t)=V_p \sin\!\big(2\pi f t+\varphi_v\big) \) or, in a more formal way of defination, as physically realizable periodic waveforms and to be decomposed in a more formal approach by Fourier series as \( i(t) = I_{\mathrm{avg}} + \sum_{k=1}^{\infty} I_k \sin\left(k \omega t + \theta_k\right) \) 

Just like a sine wave that is characterized by its smooth and oscillatory nature, an AC electrical power system typically repeats its sinusoidal waveform 50 or 60 times per second, or say, at a frequency of 50 Hz or 60 Hz

fundamental AC power waveform 50hz 60hz A stacked comparative waveform plot against a dark grid background. The top graph displays a green 50 Hz fundamental frequency sine wave measuring voltage from -1.0V to 1.0V. The bottom graph displays a cyan 60 Hz fundamental frequency sine wave over the same 0 to 0.10 second time scale, illustrating the frequency and cycle differences between standard AC power grids.
50Hz and 60Hz Fundamental Waveform

Harmonics are voltages or currents with waves form that, compared to that of fundamental ones that come with ideal frequency of 50 Hz or 60Hz, vary typically from both the ideal sinusoidal shape and with frequencies that are with integer multiples and greater than that of the fundamental waveforms. Examples as below:

  • Harmonics with 150 Hz frequency (third harmonic) compared with 50 Hz as that of fundamental waveforms
  • Harmonics with 180 Hz frequency (third harmonic) compared with 60 Hz as that of fundamental waveforms
Waveform plot displaying harmonic distortion over a 0.10 second time axis. A solid green line represents the 50 Hz fundamental frequency with a peak amplitude of 1.0V, while a dashed purple line represents the 150 Hz third harmonic with a smaller amplitude of 0.5V, illustrating how harmonic components overlay onto base AC signals.
150Hz Third Harmonics & Fundamental Waveform
Voltage waveform comparison showing a 60 Hz fundamental sine wave and a lower-amplitude 180 Hz third harmonic over time.
180Hz Third Harmonics & Fundamental Waveform
triple harmonics and fundamental waveform plus - Comparison of distorted voltage waveforms produced by combining a 50 Hz fundamental with a 150 Hz third harmonic and a 60 Hz fundamental with a 180 Hz third harmonic.
Fundamental Waveform Plus Harmonics

Harmonic Orders, Harmonic Sequencing and Effect of Harmonics

You may have noticed that we mentioned the term of “third harmonic” in the last chapter, which represents how harmonics are classed according to their order on the basis of their multiples of the fundamental frequency [3]. In general there are two types of them.

Odd-order harmonics

Odd-order harmonics are harmonic components whose orders are odd numbers, such as the 3rd, 5th, 7th, and 9th harmonics (relative to the fundamental, or 1st harmonic).

Mathematically, if the fundamental frequency is \( f_{1} \), the frequency of an odd-order harmonic is:

\[
f_{n} = (2k + 1) \cdot f_{1}, \quad k = 1, 2, 3, \dots
\]

Characteristics and effects of odd-order harmonics

  • Commonly generated by nonlinear loads such as rectifiers, variable frequency drives (VFDs), and fluorescent lamps.
  • Can cause waveform distortion, increased equipment heating, and communication interference.
  • In three-phase systems, the 3rd harmonic (and its integer multiples) can accumulate in the neutral conductor, leading to neutral overloading.

Even-order harmonics

Even-order harmonics are harmonic components whose orders are even numbers, such as the 2nd, 4th, 6th, and 8th harmonics.

Mathematically:

\[
f_{n} = 2k \cdot f_{1}, \quad k = 1, 2, 3, \dots
\]

Characteristics and effects of Even-order harmonics

  • In an ideal, symmetrical AC system, even-order harmonics are naturally cancelled out, so they rarely appear under normal conditions.
  • The presence of even-order harmonics usually indicates waveform asymmetry or the existence of a DC offset.
  • Generally less harmful to the power system than odd-order harmonics, but can cause DC bias and magnetic saturation in transformers, motors, and other equipment.

Second-Order Harmonics

Second-order harmonics are even-order ones and the frequencies of which are twice the fundamental waveform frequency, that is, 100 Hz compared to 50 Hz or 120 Hz compared to 60 Hz.

Fundamental waveform with second order harmonics - Two voltage waveform plots comparing 50 Hz and 60 Hz fundamental sine waves with their corresponding 100 Hz and 120 Hz second-harmonic components.
Fundamental Waveform with Second-Order Harmonics
second order harmonics in complex wavform - Two stacked waveform graphs comparing 50 Hz and 60 Hz fundamental sine waves with complex second-harmonic components at 100 Hz and 120 Hz, respectively, where the dashed harmonic waveforms show changing amplitude patterns across the 0 to 0.10 second interval.
Fundamental Waveforms with Complex Second-Order Harmonics

One consequence of second-order harmonics can be that, when the fundamental waveform gets to zero, the harmonics reach its high value that will cause reverse direction and lead to negative current flows in the electrical circuit. An example of such sequencing is shown as per below diagram.

Devices such as inductive motor will confront negative sequencing current which in turn opposes its rotation of magnetic field, as result of which can be a lower mechanical torque. [4]

second order harmonics with complex waveform and fundamental to show reverse sequencing - Graph of a 50 Hz fundamental voltage waveform, a dashed 100 Hz second-harmonic component, and the resulting combined waveform over 0 to 0.06 seconds, showing unequal positive and negative peak amplitudes caused by the negative-sequence harmonic effect
Second-Order Harmonics Causing Reverse Current Flow in Circuit

Third-Order Harmonics

Third-order harmonics come with a frequency of 150 Hz if the supply is of a 50 Hz fundamental waveform.

third harmonics with fundamental waveform - Voltage-versus-time graph showing a 50 Hz fundamental sine wave and a dashed 150 Hz third-harmonic waveform over 0 to 0.06 seconds, illustrating the higher-frequency third harmonic associated with a zero-sequence effect.
Third-Order Harmonics with 50Hz Fundamental Waveform

Alternatively known as triplens, third-order harmonics are dangerous in some situations. From the diagram shown above, both the fundamental waveform and the third harmonics reach zero and high value at the same time despite that the peak points are opposite to each other.

For example, at 0.015 of the time (s) axis, the voltage of harmonics and fundamental one is at their highest value but opposite to each other, creating a zero-sequence current and neutral voltages in the power system. 

Fourth-Order Harmonics

In the case of a 50HZ fundamental waveform added with fourth-order harmonics which is of 200Hz frequency, the power systems see increased current to flow in the circuit which further increases the heat generated from the power system.

Graph comparing a 50 Hz fundamental voltage waveform, a dashed 200 Hz fourth harmonic, and the resultant waveform from 0 to 0.06 seconds, with the fourth harmonic completing four cycles for each fundamental cycle.
Forth-Order Harmonics with 50Hz Fundamental Waveform

The diagram above shows that the traces of waveforms, both the fundamental and the harmonics, reach their highest value at the same time at bot negative and the positive cycle. Following the Ohm’s law when the loading impedance is that same while voltage of supply and harmonics get overlaid, RMS current gets higher and subsequently leading to increased power and electrical loading in the system.

Harmonic Sequencing and Effect of Harmonics

DesignationFrequency (Hz)SequenceRotationEffect of Harmonic
Fundamental (1st)50+ForwardNormal operation
2nd100–ReverseReduction of motor torque
3rd1500NoneHeating by adding voltage and current in the neutral
4th200+ForwardOverheating effects
5th250–ReverseReduction of motor torque
6th3000NoneHeating by adding voltage and current in the neutral
7th350+ForwardOverheating effects
8th400–ReverseReduction of motor torque
9th4500NoneHeating by adding voltage and current in the neutral

Note: For a 60 Hz fundamental, harmonic frequencies are calculated using the same method: frequency = harmonic order × fundamental frequency.

Verifying Compliance by Harmonics Injections with ActionPower’s AC Power Supply and Grid Simulators

We wish our explanations above have clarified to details what are harmonics and their impacts of electrical power systems.

At ActionPower, we design and manufacture high-performance programmable AC power supplies and grid simulators engineered for advanced power quality and harmonic testing. Our solutions allow precise harmonic injection, whether single-order, multiple-order, positive, negative, or zero-sequence components, fully compliant with international standards such as IEC 61000-4-7, IEC 61000-4-13, and IEEE 519.

To acquire further information about our AC power sources and grid emulators, click the following badges to access our product page:

Validate utility-scale ESS, Inverters and PCS with MVA platform of regenerative grid simulator from where harmonics and interharmonics are injected to the former for adaptability validation.

MVA High-Power Grid Simulator

Cabinet type programmable power supply with module-based architecture for covering grid-adaptability test of sub-systems with power ranges from hundreds of kW towards intermediary MVA power range.

Check PRO20 Four-Quadrant AC Source-Load

CORTEX AC Programmable Power Supply is available for AC-source side testing providing flexible user-defined waveform generation and sequence automation options, built on rack-mount modular chasis and ideal for bench-top and laboratory testing applications.

Rack-Mount Modular Programmable AC Source

Bibliography

  • [1] Understanding Power System Harmonics, Prof. Mack Grady, Dept. of Electrical & Computer Engineering, University of Texas at Austin, link
  • [2] Charles Proteus Steinmetz, From Wikipedia, the free encyclopedia, link
  • [3] Harmonics in AC Power Systems, Monolithic Power, link
  • [4] Mitigating Harmonics in Power Systems, May 04, 2023 by Simon Mugo, EE Power, link

 

 

 


ActionPower research and development team

Talk to ActionPower

From ActionPower we are open to listening to your suggestions and opinions.

For further media contact or consultation about any topics which might be of your interest about our company, you will be welcomed to send us an email to:

info@actionpowertest.com

Latest News


PRL DC Load Simulator Introduced by ActionPower for AI Server Workload Validation

Dynamics and power regeneration are no longer compromise to each other. Adopting innovation topology technologies is the PRL DC Load Simulator that accommodates ultra-fast dynamics, regenerative load and high-power scalability from a united single system.



ActionPower to Debut MIX Series Hybrid Power Supply at Europe Automotive Testing Expo 2025

The latest hybrid programmable power supply by ActionPower comes with 6 channels hybrid interface and allows AC/DC module arbitrary combination for flexible testing configuration where both AC and DC are...



CONTANCT US

Zhiwei Bao, SEO Engineer and technical copywriter at ActionPower
About the Author

Zhiwei Bao

Industrial Automation Power Electronics Product Marketing Field Application

Zhiwei Bao holds 20+ patents in the field of mechanical engineering and is keen on industrial automation and product marketing. His interdisciplinary background, along with his passion and initiative for learning, has led him to a profound understanding of power electronics. He manages the technical copywriting for programmable power and testing topics at ActionPower through product-marketing-driven approaches.

About Zhiwei Bao

Explore More

diesel generator and data center for AI facility

The Surge in AI data Center Construction is the Boom in Industrial...

Figures of Soaring AI Data Center Construction Following AI Boom Public available data shows the investment to data center construction...



Why Linear Loads Demonstrates Better Dynamics Performance than Regenerative Ones? And How ActionPower Breaks the Boundary?

Why Linear Loads Demonstrates Better Dynamics Performance than Regenerative Ones? And How...

Conventional testing applications where programmable electronic loads are deployed used to see a definite trade-off between dynamic performance and the...



combination of software and hardware is battery cycler's key feature

Grid Code Compliance Test Explained: What to Validate and Which Standards to...

Facing the modern grid landscape is the ever more important grid interconnection and interoperability, since DERs are now enacting as...




Get in Contact

Global Contact

Sales Network & Locations

If you are looking for an automated test system to validate your products during development and research stages to make sure of their successful commercial launch, ACTIONPOWER will be at your disposal to study your specifications and requirements to provided either standard or customized testing solutions.

Product Inquiry

Specification-matching testing and simulation solutions need discussion of both parties. Actionpower welcomes you inquirt to study together with us about how we can automate your testing processes.

Send Inquiry

Trade Shows & Events

These are the upcoming events and places you can find ACTIONPOWER and talk with us face-to-face!

Check Events

Social Media

Follow us to keep updated of our innovations.

LinkedInTwitter
Quick Model Access

Smart Discovery

Access our Power Supply Wizard to find the right programmable power supply for your use cases and testing scenarios.

discover programmable power supply by filtering with current, voltage and power ranges
CONTACT US

Contact Us

Professionalism is what we care about. Why not email us with your technical requirements fully explained rather than submitting a simple message so that we revert more proactively with detailed solutions?

Subscribe to Newsletter

Thank you for subscribing!