Find out the latest innovations from ActionPower
Modern power systems, integrated with microgrids [1] and Distributed Energy Resources (DERs), have shifted their operational mechanisms from centrally-dominated architectures to complex, inter-coupled ecosystems. In these systems, numerous inverters interfacing renewable sources must be precisely synchronized and harmonized to ensure grid stability.
Then the fundamental question emerges: Who commands the grid’s key metrics like voltage and frequency – and among the interconnected sources who is tasked with comply with the collective pulse?

What underpins the balancing among sub-systems on the grid and implied here is the coordination of grid-forming and grid-following controls, which defines the grid’s resilience from micro-level harmonic suppression to system-level inertia support and black-start capability. With this article, we break into the technical boundary between grid-forming and grid-following technologies, how they strike a balance between each other to form the modern resilient grid with complex DERs, and how programmable power supports the validation of their performance and reliability.
To understand the roles of Grid-Forming and Grid-Following technologies, one must first revisit the foundational distinction between how power is controlled and injected into a system. At its core, this is a transition from voltage source behaviour to current source behaviour.

Fig 1. Circuit Diagrams of Grid-Forming and Grid-Following Inverters
A current source is an electronic device or circuit that delivers a constant, fixed amount of electric current to a load, regardless of the voltage across it. [3]
Inverters interfacing renewable energy with the grid generally operate as followers that synchronize to the grid’s pre-defined voltage and frequency – the process is governed by a Phase-Locked Loop (PLL) [2] that tracks the phase angle at the Point of Common Coupling (PCC). Consequently, in the event of an outage or accidental islanding, these systems fail to sustain operation due to the absence of an autonomous reference to maintain the system’s stability.
Grid-forming technology, on the contrary, emerges as the solutions facing this vulnerability of grid-following systems and allows inverters to act as independent voltage sources that can sustain the grid even when the external reference is lost.
A voltage source is an electronic device that provides a constant electrical potential difference to drive current through a circuit.
In the context of the grid-forming technology such as a GFM energy storage system, the inverter functions as an independent voltage source that defines the foundational grid parameters and thus sustain the system operation by modulating the release of stored energy. What is emulated here, in this case, is the mechanical inertia and damping characteristics of traditional synchronous generators. [4]
Grid-forming technology does not simply maintains regional stability but also provides critical frequency support and oscillation mitigation during large-scale disturbances.
Extending the topic from the above clarification regarding the nature of grid-forming and grid-following operations, their stability, and resiliences against certain variety of grid anomalies and disturbances such as voltage sags, frequency deviations, weak-grid oscillations, and grid restoration events.
The following table specifies several common scenarios and explains how each control strategy responds.
| Grid-Following | Grid-Forming | |
|---|---|---|
| Voltage Sag & Fault Ride-Through (LVRT) | PLL-Dependent Current Control: Operates as a current source synchronized by PLL. Deep voltage sags or phase jumps may cause PLL loss of lock, leading to unstable current control or protective tripping. | Voltage Source Behaviour: Maintains an internal voltage reference and injects reactive current according to the PCC voltage deviation. Phase reference remains stable during deep sags, enabling effective voltage support. |
| Weak Grid Conditions (Low SCR) | Stability Limited by Grid Impedance: Strong coupling between PCC voltage and current control loop. Low SCR conditions may trigger PLL-induced oscillations, particularly when multiple units operate in parallel. | Voltage Reference Establishment: Forms a controlled voltage source through power synchronization control. Provides damping to voltage oscillations and maintains stable operation in very low SCR networks. |
| Frequency Disturbance & Power Imbalance | Frequency Tracking: Follows grid frequency through PLL. Power response depends on external commands and delayed measurements, providing limited inertial response during disturbances. | Inertia Emulation: Implements swing-equation-based control to adjust frequency according to active power imbalance. Provides virtual inertia and damping to limit ROCOF and frequency nadir. |
| Blackstart & Grid Restoration | Grid Reference Required: Requires an existing voltage vector for PLL synchronization. Cannot energize a dead bus or establish system voltage and frequency independently. | Autonomous Grid Establishment: An internal oscillator defines voltage magnitude and phase during the blackstart. Capable of energizing a dead bus and providing the voltage-frequency reference during system restoration. |
The fundamental purposes of validating grid-forming inverter with programmable power is about how the former reacts to complex and shifting anomalies while generating virtual inertia and adaptability to non-ideal SCR and \(V/f\) conditions.
A grid simulator, in this case, is supposed to not simply function as a four-quadrant programmable power supply with bidirectional flow capability, however, to replicate with user-defined and controllable way miscellaneous emulated grid conditions through, not only configurable voltage and current, but advanced situations such as phase and frequency deviations, RLC-modelling based impedance simulation, etc.

Fig 2. Testing Sequence Setup for Inverter’s Grid-Forming Capability Validation
Advanced grid simulators utilize Virtual Impedance Emulation to dynamically regulate the grid characteristic model defined by
$$Z(\omega) = R + j\omega L + \frac{1}{j\omega C}$$
calculating the real-time voltage output as
$$V_{\text{out}} = V_{\text{ref}} – Z_{\text{grid}} \cdot I_{\text{DUT}}$$
Furthermore, integrated profile emulation software supports the direct input of the Short Circuit Ratio (SCR), through which the control loop automatically derives the equivalent grid impedance via the relationship
$$Z_{\text{grid}} = \frac{V_{\text{nom}}^2}{SCR \cdot S_{\text{rated}}}$$
Grid-forming inverters are supposed to provide robust voltage support during the events of LVRT and HVRT without losing synchronization
Challenges proposed and as per those testing requirements specified in IEEE 1547.1 is fundamentally about the grid simulator’s high response and dynamics which, in specific, the slew rate to replicates and executes the rapid voltage dips and swells with symmetrical faults (Phase-to-Phase or Single-Phase-to-Ground)
Verification of the swing equation implementation requires the grid simulator to execute high-precision frequency transients.
A grid-forming inverter has an integrated modelling and algorithm that equates the inertia of synchronous generator following the equation:
$$ J\frac{d\omega}{dt} = P_m – P_e – D(\omega – \omega_0) $$
against which the grid simulator should reproduce high-precision and dynamically controlled frequency transients – such as frequency steps, ramps, and RoCoF events – with high temporal resolution and waveform accuracy, to validate whether the inverter reacts and adjusts its output frequency according to its configured virtual inertia and damping characteristics when an active power imbalance occurs in the system
Validating the voltage and reactive power regulation capability of a grid-forming inverter is challenging for utility-scale grid simulators because the inverter actively establishes the PCC voltage rather than following an external reference.
To assess the Q–V droop or voltage control behaviour, the simulator must impose controlled disturbances such as voltage offsets, programmable grid impedance, or dynamic voltage steps while maintaining system stability. The inverter response is then evaluated based on voltage regulation accuracy, reactive power response, and dynamic stability, particularly under weak-grid conditions where PCC voltage becomes highly sensitive to reactive power injection.
With a proven track of testing applications and use case in the field of renewable energy and grid-forming ESS, ActionPower is by your side to address these validation challenges with our utility-scale MVA-level grid simulators capable of reproducing realistic grid conditions for both grid-following and grid-forming inverter testing.
Instead of relying solely on controller-level emulation, ActionPower’s grid simulators creates a controllable electrical environment where voltage, frequency, grid impedance, and short-circuit ratio (SCR) can be precisely defined as if at the point of common coupling in the real-world scenarios.
To discover more information about our solutions, you may either contact us, or visit our solution page of grid emulation.

Zhiwei Bao holds 20+ patents in the field of mechanical engineering and is keen on industrial automation and product marketing. His interdisciplinary background, along with his passion and initiative for learning, has led him to a profound understanding of power electronics. He manages the technical copywriting for programmable power and testing topics at ActionPower through product-marketing-driven approaches.
About Zhiwei Bao
If you are looking for an automated test system to validate your products during development and research stages to make sure of their successful commercial launch, ACTIONPOWER will be at your disposal to study your specifications and requirements to provided either standard or customized testing solutions.
Specification-matching testing and simulation solutions need discussion of both parties. Actionpower welcomes you inquirt to study together with us about how we can automate your testing processes.
Send InquiryThese are the upcoming events and places you can find ACTIONPOWER and talk with us face-to-face!
Check EventsProfessionalism is what we care about. Why not email us with your technical requirements fully explained rather than submitting a simple message so that we revert more proactively with detailed solutions?