Grid Interconnection Testing for SST (Solid State Transformer) as Associated Power System Interface of ESS-Integrated AI Data Center
PUE (Power Usage Effectiveness) is the underlying very specification that contributes to the innovations in architectural development for AI Data Center.
From UPS-backed topology prevailing nowadays to the HVDC structure which is re-shaping the industry and towards the futuristic SST (Solid State Transformer) integrated one, the only ambition that data centers follow with these changes is to utilize the utility power as maximum as possible at the load side of GPU clusters.
This application note covers the architectural evolvements of AI Data Center and extends to topic to SST as the power interface between grid and the server side, accordingly then to study how grid interaction standards may apply regarding their testing and validation.
| Version | 1.0.0 |
|---|---|
| Categories | AI Server |
| Download | Download Application Note |
| Download Count | 3 |
| Page Views | 688 |
| Size | 1.12 MB |
| Create Date | 04/09/2026 |
| Last Updated | 04/11/2026 |
| Author | Zhiwei Bao |
| Reviewed | Sen Wang |
Energy efficiency is the inevitable concern that overrides primarily other factors when it comes to building an AI facility. Training, testing and serving, the functioning of AI GPU cluster undergoes through its lifecycle featured by shifting electrical characteristics, extreme power volatility and high magnitude during peak load.
The underlying metric of PUE (Power Usage Effectiveness) is the reason for which AI data centers are being redesigned in their architecture. To summarize, the ultimate goals are keeping the numbers of power stage as few as possible so that less power are lost during conversions [1] and that the GPU cluster consumes as much as possible the power fed to the facility. Further with the integration of renewable energy sources such as PV and BESS, AI server data center is locally formed into a micro-grid, either of DC-bus or AC-bus, dependent on its architecture, and considered a DER that connected to local grid through power system interfaces. As a result, data center is no longer any kind of systematically standalone facility, but something subject to compliance to grid interoperability standards and codes.
Growing Server Rack Power Rating is Forcing Architecture to Take Transformation
Staring by citing the article of Qishan Pan, a community member at Infineon [2], the computing power of data center is no longer the same as that of the web 2.0 age.
Nevertheless, data centers are experiencing a massive surge in power demand. Compared to 2022, when GPUs consumed around 0.4kW and a single rack reached only 60kW, current GPUs in 2026 draw 2-4kW each, pushing rack-level power to 1MW.

Fig 1. The Growing Power Demand of Processors (xPUs) and Server Rack for Data Center
Meanwhile that the UPS as the power interface against MVAC local utility is still a prevailing option or AI data center facility, the growing power rating towards 1MW has led to two primarily concerns by which the transition of architecture is no longer a topic of the future.
Stage Losses along the Architecture Scale Correspondingly as Rack Power Grows
The LVAC-UPS-supported was inherited from the age of web 2.0, while applied to AI data center it still relies on a multi-stage AC-to-DC conversion chain to convert the grid AC down to the voltage that fits the demands of server PSU before the latter backs the functioning of GPUs.
The topology below demonstrates the power stages followed where utility AC is converted to 54 VDC along the data center. Tracing the power path from the LV MSB to the Rack PSU in the diagram, we can map out the typical operational efficiency \(\eta\) of each tier under full load, supposing that it is a 1MW server rack:
- LV MSB to LVAC UPS (Distribution & Rectification): Double-conversion AC-to-DC-to-AC systems operate at an efficiency of approximately \(\eta_1 = 94.5\%\).
- PDU (Distribution Transformer): Step-down transformation introduces minor core and copper losses, averaging \(\eta_2 = 98.0\%\).
- AC Distribution to Compute Rack PSU \(415\text{ VAC}\) to \(54\text{ VDC}\): The server-level power supply unit rectifies and steps down AC to low-voltage DC with an efficiency of \(\eta_3 = 96.0\%\).
The cumulative end-to-end efficiency \(\eta_{total}\) of this traditional chain is calculated as the product of all individual stage efficiencies:
$$\eta_{total} = \eta_1 \times \eta_2 \times \eta_3 = 0.945 \times 0.980 \times 0.960 \approx 0.889 \text{ (or } 88.9\% \text{)}$$
To deliver a net compute power of \(1,000\text{ kW}\) \(1\text{ MW}\) to the AI compute rack, the total power that must be drawn from the upstream grid \(P_{input}\) is:
$$P_{input} = \frac{P_{rack}}{\eta_{total}} = \frac{1,000\text{ kW}}{0.889} \approx 1,125\text{ kW}$$
Consequently, the absolute power lost as heat across these intermediate conversion stages \(P_{loss}\) is:
$$P_{loss} = P_{input} – P_{rack} = 1,125\text{ kW} – 1,000\text{ kW} = 125\text{ kW}$$

Fig 2. 415 VAC Distribution AI Server Data Center Architecture Today with LVAC UPS
The \(P_{loss}\) stands for the energy which is totally burned off as heat along the distribution and stages across the UPS, PDU, and rack PSUs, almost equivalent to running an additional high-density server rack completely dedicated to generating thermal waste.
Respectively the facility has to implement cooling devices for handling the heat. Yet this proposes further energy consumption for load at the HVAC and cooling. For example, supposing a cooling system operates at a Coefficient of Performance (COP) [3] of 3.0, removing the conversion heat demands an extra \(41.7\text{ kW}\) of auxiliary power.
In LV Architectures for MW Racks, Current Scales and Physical Constraints Surface
Another of the noting downsides of grading down LVAC power from UPS to the rack at 48 VDC (or even 12 VDC in older designs) is the current issues. It is easy to figure out the reason by solving with Ohm’s law, supposing a 1MW rack backed by 415 VAC Distribution :
$$I = \frac{P}{V} = \frac{1,000,000\text{ W}}{48\text{ V}} \approx 20,833\text{ A}$$
Respectively to prevent these busbars from melting due to resistive heating \(I^2R losses\), the cross-sectional area of the copper must be dramatically increased. As noted by NVIDIA, a single 1MW rack can require up to 200 kg of copper busbar [1], suggesting an exponential CapEx increase and especially when the data center scales up, for example, to a 1-Gigawatt facility.
HVDC and SST-Backed Architecture Transfers AI Data Center Brinds 800VDC Directly to Server Rack
With above concerns bore in mind, the future data center architecture design then focusses on two facts which are eliminating power conversion stages as possible and maintaining high voltage when the supply down to the load side of server rack. [4]
Current hybrid architectures utilize 800VDC server racks. Prior to reaching the rack, upstream stages step the utility MVAC down to LVAC and rectify it into an 800VDC distribution link. Now that higher voltage is supplied towards the server side, current demand is reduced and thanks to which resistive loses are reduced with power transfer more efficient.

Fig 3. Transitional HVDC Architecture with 800 VDC Server Rack
While the hybrid model improves efficiency and effectiveness, it still relies on stepping down the 13.8–35kVAC network to 480VAC before rectifying it to DC. To completely eliminate these redundant low-voltage converters and rectifiers, the ideal architecture must convert MVAC directly to 800VDC, which is what exactly the industry has been envisioning.

Fig 4. SST Integrated Data Center Stepping MVAC Directly Down to 800VAC
The discovery of SST’s potential match to the concerns around AI server data center is not a coincidence. The pursuit after a “high-frequency link converter” traces long back to half a century ago, and it is only until the commercialization of wideband gap semiconductors, specifically Silicon Carbide (SiC) MOSFETs that high-power SSTs was finally made a reality. [5]
Evolving from Simply a Data Center into a DC-Bus Micro-Grid with SST as Power Interface
Further to prevent the data center from downtime or shutdown due to the grid being the single source counted on, the facility can be integrated as well with renewable energy sources such as solar farms, fuel cells, and even with a BESS, which can store energy for the facility to ride through potential grid outages.
The main bus maintained by the SST that supports the server cluster ideally becomes one that matches the native DC output from these renewable sources. By keeping the power in the form of DC and avoiding the integration of inverters – which would further trigger energy losses – it forms a DC-bus based micro-grid that, in turn, can either support the utility grid or feed the server data center’s operations.

Fig 5. AI Server Data Center Integrated with Renewable Energy Sources and Backed by SST – Forming a DC-Bus Micro-Grid
SST as Power System Interface in Relation to Grid Interconnection Standards and Testing Applications
Once at facility level the data center is integrated with solar farm and especially BESS to either support the server side operation or in turn to inter-operate with the grid, the feature of bi-directional flow turns the whole facility into a micro-grid based on DC-bus and then categorized as DERs defined by IEEE 1547-2018 [6], with SST respectively falling into the category of power system interface.
The OCP Solid-State Transformer (SST) Specification officially states in its scope of application that a Medium Voltage Solid-State Transformer (MVSST) is defined as a megawatt-scale power electronic converter, which when coupled with energy storage could function as a Medium Voltage Uninterruptible Power Supply (MV-UPS). Beyond basic transformation, the SST provides advanced grid-interactive capabilities such as programmable MVAC response compliant with evolving grid codes. [7]

Fig 6. OCP Solid-State Transformer (SST) Specification
Consequently, the upstream MVAC interface of the SST serves as the critical boundary where applicable grid code compliance testing must be conducted, while simultaneously validating the dynamic response of the coupled LVDC-ESS side. That is, in the context of testing with programmable power, simulating utility with a grid simulator while a battery simulator being tied to the SST’s LVDC-bus for replicating ESS behaviour.

Fig 7. Testing Topology Demonstrating ActionPower’s Solutions for SST from MVAC and HVDC-Bus
Currently, grid code testing for SST in the context of serving micro-grid while integrated with ESS serving as voltage source has not seen a unified standard, given the fact that the approach to SST as power interface is still at the stage of being a prototype pending commercialization.
Applicable testing regulations and standards that can be referred to for the moment are IEEE 1547 (DER Reference), IEEE 2800 (DER at transmission level), ITIC (classic PSU ride-through), and among others, MISO and those by other utility authorities. For specific testing applications, engineers must adapt the relevant clauses from each of these respective standards.
Voltage Ride Through Capability Testing for SST as Power Interface of DC-Bus Micro-Grid
The OCP SST Design Specification refers to ERCDT graph for defining the SST’s capability of voltage ride-through [8]. In essence, it is as well at test engineer’s discretion which specific criteria to adopt for their application. Regarding the equipment and hardware, the testing setup requires accordingly a grid simulator with voltage stepping function that inject anomalies to SST’s MVAC-bus meanwhile that an ESS battery simulator reproduces either current-source or voltage-source behaviour different transient context.
- Over-Voltage Ride-Through (1.1 pu < x ≤ 1.2 pu): When the SST experiences an input voltage above its nominal value, the interface must dynamically draw proportionally less current from the utility grid to maintain a constant 100% rated power output to the AI servers.
- Acceptable Power Quality Range (0.9 pu ≤ x ≤ 1.1 pu for continuous operation ∞): Within this nominal voltage range, the SST must remain fully functional and continuously supply 100% of the rated output load without any time constraints.
- In Low Voltage Ride-Through range (0.5 pu < x < 0.9 pu): When utility voltage drops within this range while the SST must supply 100% of the rated output load, the coupled ESS functions as a current source to sustain the operation. This prevents the SST from drawing current far beyond its nominal rating, avoiding potential system damage.
- In worse Low Voltage Ride-Through range (x < 0.5 pu): Maintaining the SST as the voltage source to withstand such anomalies is no longer safe, as the input current would surge far beyond the nominal rating. The SST must detect the condition and draw no input current, leaving the coupled ESS to function as the sole voltage source for the system.

Fig 8. SST and ESS Operational Transitions during Transient Grid Events.
The Shaded Regions Define the Critical Ride-Through Limits (LVRT Range #1 and #2)
before Intentional Islanding or Facility-Level Actions are Required
Anti-Islanding Test Capability for SST in the Event of Grid Outage
Anti-islanding testing is not among the criteria stated in the OCP SST Design Specifications, however, its implementation is inevitable. Once the SST acts as the facility-level power interface connected to the utility grid, especially with an integrated ESS, the deployment becomes strictly subject to authority interconnection requirements such as IEEE and FERC.

Fig 9. System-Level Testing Topology for SST Grid-Code Compliance
Utilizing Grid Simulator with Integrated RLC Modelling and ESS Battery Simulator
Another of ActionPower’s application note introduces technically to detail the definition and application anti-islanding test for inverters and PCS, which are defined as well as power system interfaces for DERs, according to IEEE and UL.
Dynamic Server Load Capability Testing in Coupling with Grid Simulator
In the strictest sense, dynamic load transient testing does not constitute a specific conformance test under IEEE 1547, which primarily addresses the interconnection and interoperability of distributed energy resources (DERs) with electric power systems. Nevertheless, an SST serving a data center or microgrid should possess sufficient transient response, overload capability, and control robustness to accommodate rapid and large step changes in load demand.
If such load transients are not adequately managed, they may result in excessive voltage deviations, degraded power quality, DC-link disturbances, or unintended activation of system protection mechanisms.

Fig 10. Standalone Dynamic Load Testing Topology. The SST is Directly Subjected to
Extreme AI Server Load Transients via the DC Load Simulator without ESS Buffering
Validating its Internal Control Bandwidth and Bare-metal Resilience
ActionPower’s Utility-Scale Programmable Power for AI-Data-Center-Purposed SST
To accelerate the implementation of MW-level server racks and foster surrounding power systems where the SST stands out as a key breakthrough, ActionPower provides a robust portfolio of utility-scale testing solutions. We stand ready to address your SST testing requirements, covering both grid-side compliance and 800VDC load simulation – to thoroughly validate system robustness against extreme GPU workload transients.
Regenerative Grid Simulators
Various models of high-power grid simulators match the testing requirements for SST from its MVAC-bus through our additional solutions of integrated voltage-stepping function, with power capability spanning up to 10MVA, capable of replicating complex medium-voltage AC grid abnormalities, deep LVRT profiles, and real-time resonant RLC behaviors to ensure strict adherence to international utility standards like IEEE 1547.
Tailored for Solid-State Transformers (SSTs) and grid-interface testing in AI Data Centers (AIDC), the TITAN series delivers scalable power from 300 kVA to 1 MVA per cabinet and scales up to 10 MVA total capacity. It expertly replicates complex medium-voltage grid abnormalities, deep LVRT profiles, and real-time resonant RLC behaviors for strict IEEE 1547 compliance.

AI Server DC Load Simulators
Purpose-built to subject the 800V DC bus to authentic, worst-case GPU workload transients, verifying bare-metal control bandwidth, DC-link capacitance margins, and overall system resilience without requiring immediate physical infrastructure. For more information, check PRL High-Dynamic DC Load Simulator.
Regenerative DC Load accommodating high dynamics and fast response that aligns with the complex and shifting emulation requirements for data-center-related load testing. PRL scales up from a single 5U/25kW to 1.4MW high-power testing platform with 8 cabinets in parallel connection while offering regenerative load capability of up to 85% to save your testing energy cost.

For further information about our technical approach to grid compliance testing, you may either submit a contact form or reach out to our field application team by sending an email.
Bibliography
- [1] Data Centers Are Transitioning From AC to DC 800-volt DC power delivery will enable next-gen AI data centers, IEEE Spectrum, Drew Robb, Mar 24, 2026, Link
- [2] 800V AI服务器机柜的DC/DC电源架构, Infeneon, Qishan Pan, 27 May 2026, Link
- [3] Coefficient of performance, Energy Education, Link
- [4] NVIDIA 800 VDC Architecture, Power Delivery for the AI Servers and Factories of the Future, NVIDIA, Link
- [5] Solid-State Transformers Emerge for Next-Gen AI Data Centers, ET Datacenters, Sep 01, 2026, Link
- [6] IEEE 1547-2018, IEEE Standard for Interconnection and Interoperability of Distributed Energy Resources with Associated Electric Power Systems Interfaces, Link
- [7] Solid State Transformer (SST) Specification, Revision 0.3.0, Specification Effective, 6/22/2026, Author: Google, Microsoft, Nvidia, Link
Medium Voltage to 800 VDC Power Conversion Platform - [8] Texas PUC approves ‘ride-through’ rules for data centers, Utility Dive, Diana DiGangi, uly 13, 2026, Link
- [9] Sina Mohammadi, Wayne Wang, Marcus Chen I Wada, Rouzbeh Haghighi, Ali Hassan, Hualong Liu, Archit Bhatnagar, Ang Chen, Wencong Su, Grid integration of AI data centers: A critical review of energy storage solutions, Advances in Applied Energy, Volume 23, 2026, 100291, ISSN 2666-7924, Link

Zhiwei Bao
Zhiwei Bao holds 20+ patents in the field of mechanical engineering and is keen on industrial automation and product marketing. His interdisciplinary background, along with his passion and initiative for learning, has led him to a profound understanding of power electronics. He manages the technical copywriting for programmable power and testing topics at ActionPower through product-marketing-driven approaches.