Use ActionPower’s Helion Programmable Power Supply to Test Micro-Inverter with Flexibility and Facilitated Test Topology
| Version | V1.0.0 |
|---|---|
| Categories | PV Testing |
| Download | Download Application Note |
| Download Count | 15 |
| Page Views | 1679 |
| Size | File not found |
| Create Date | 21/07/2025 |
| Last Updated | 04/11/2026 |
| Author | Zhiwei Bao |
| Reviewed | Sen Wang |
What are Micro-Inverters?
Inverters are the key components for converting the DC (Direct Current) generated by solar panels into AC (Alternating Current) that matches what home appliances and national grid use. Without inverters, let them be in form of string-inverter or micro-inverter, energy generated from solar arrays will be useless.

Fig 1. Micro-inverters are attached to each unit of solar panel
Micro-inverters, in difference to traditional string inverters that converts the output from all the panels within the system through one single channel, micro-inverters are more flexible and attached to each unit of solar panel to execute the conversion since the outset of the solar energy generation topology, in a way of independent conversion.
What are the Advantages of Micro-Inverters?
Micro-inverters follow a different pattern of operation compared to traditional string or central inverters, to which electricity generated from the solar panel is converged and converted together into alternating current. Such a kind of difference features micro-inverter with advantages at both unit and system level from which the solar energy generation can benefit and achieve more efficiency.
MPPT at Individual Unit Level rather than Collectively
Each micro-inverter is connected to a single solar panel and has its own Maximum Power Point Tracking (MPPT). This optimizes the power output of each panel independently, even if some panels are shaded, dirty, or have slightly different characteristics. With string inverters, the output of all panels is limited by the weakest panel in the string.
System Tolerance and Negative Weather and Sunlight Condition Mitigation
In contrast to string inverters that serves as a single point of conversion and limited by the output from the weakest panel, micro-inverters take the most out of each solar panel. In case that one of the panels is 50% shaded, the rest panels among the system remain operating at full capacity without compromising the potential power, assuming that they are not shaded.
Faster Deployment and Easier System Expansion
Solar systems built with micro-inverters are typically quicker to install compared to those using traditional string inverters. Micro-inverters give you maximum flexibility: you can start with just a small system, even just a single panel, and expand it step by step as your needs grow. In contrast, string inverters require a minimum system size to operate, limiting your options. With micro-inverters, scaling your solar array is simple, efficient, and future-ready.
Testing Environment Setup for Micro-Inverters
A micro-inverter has its input side connected to the solar panel as DC source while from the output side it feeds the grid in form of alternating current. The testing may target different validation. standards and for verifying ranges of performance specifications of the micro-inverter, which might include:
- Validating the DC-AC conversion efficiency
- Validating the Maximum Power Point Tracking (MPPT) performance
- Power quality verification in terms of harmonics, total harmonics distortion (THD) and power factor, etc.
- Grid adaptability and protection verification
Yet as it is not practical to test the micro-inverter with substantial solar panels and grid now that their performance and operation status is beyond engineer’s capability of active control, devices and testing instruments like programmable DC power supplies (PV simulators) and grid simulators (programmable bidirectional AC power supply) are alternatively used to emulate the behaviours, input, and output of solar panels and utility grid.

Fig 2. Setting up testing environment for micro-inverters with PV simulator and grid simulator
Instruments at Input Side to Connect the Tested Micro-Inverter
On the input side of micro-inverter stands a DC source, referred to as either a programmable DC power supply or PV simulator, which emulates the characteristics of photovoltaic modules, or say, solar panels. Real solar panels do not behave like a constant voltage or constant current source; instead, they produce an I-V curve that changes with irradiance and temperature. A PV simulator recreates these characteristics in a controlled, repeatable way, providing realistic DC input for micro-inverters in a lab or test bench environment without the need for actual sunlight.
Validate MPPT tracking performance
One of the key validations is to assess how accurately and quickly the inverter tracks the true maximum power point (MPP) under static and dynamic PV conditions, including multi-peak I-V curves (partial shading).
Signals & Definitions
- \( V_{\mathrm{PV}}(t), I_{\mathrm{PV}}(t) \): PV input voltage/current
- \( P_{\mathrm{in}}(t) = V_{\mathrm{PV}}(t)\, I_{\mathrm{PV}}(t) \): inverter DC input power
- \( P_{\mathrm{MPP}}(t) \): theoretical MPP power at same condition
- Tracking error: \( e_P(t) = 1 – \frac{P_{\mathrm{in}}(t)}{P_{\mathrm{MPP}}(t)} \)
Key Metrics
- Static MPPT efficiency:
\[
\eta_{\mathrm{static}} = \frac{\overline{P_{\mathrm{in}}}}{\overline{P_{\mathrm{MPP}}}},
\quad \overline{X}=\frac{1}{|W|}\int_W X(t)\,dt
\] - Dynamic MPPT efficiency:
\[
\eta_{\mathrm{dynamic}} =
\frac{\int_{t_0}^{t_1} P_{\mathrm{in}}(t)\,dt}{\int_{t_0}^{t_1} P_{\mathrm{MPP}}(t)\,dt}
\] - Energy capture loss:
\[
E_{\mathrm{loss}} = \int_{t_0}^{t_1}\!\big(P_{\mathrm{MPP}}(t)-P_{\mathrm{in}}(t)\big)\,dt
\] - Settling time, overshoot, ripple \(\Delta P_{pp}, \Delta V_{pp}, \Delta I_{pp}\)
Procedures
| Scenario | Steps | Outputs |
|---|---|---|
| Static points | Load I-V curve (STC, reduced irradiance, high temp), hold 30–60s. | \(\eta_{\mathrm{static}}\), ripple values |
| Dynamic steps | Switch irradiance or curve at \(t_0\). | \(\eta_{\mathrm{dynamic}}\), settling time, overshoot, \(E_{\mathrm{loss}}\) |
| Ramps / clouds | Apply linear ramps or cloud profiles. | \(\eta_{\mathrm{dynamic}}\), error statistics |
| Multi-peak curves | Load dual/triple-peak curves, vary initial condition. | Global-MPP success rate, time-to-lock |
Instruments at Output Side to Connect the Tested Micro-Inverter
After the conversion has been completed from the inverter, the solar energy transformed into alternative current electricity is then fed to local utility grid or to home appliances. A grid simulator serves as a controllable and programmable AC source and load to coordinate with the tested micro-inverter to validate the grid adaptability of the latter. The validation from the output sides sets to purposes including whether the power from the inverter meets the grid standards, and in turn, whether the inverter can withstand grid anomalies and operate stably and avoid downtime.
Testing LVRT (Low Voltage Ride-Through) and Frequency Response
Grid suffers from frequent anomalies that will affect in turn the devices tied-up to it. Micro-inverters are supposed to withstand abnormal scenarios like low-voltage ride through (LVRT) and sometimes frequency shifts or harmonics to remain operation as how it is supposed to work.
Key Metrics
- Ride-through compliance: connection status vs. the required voltage-time profile (pass/fail envelope).
- Recovery time \(t_{\mathrm{rec}}\): time to restore nominal current/power after the disturbance.
- Frequency response: active/reactive power behavior vs. frequency deviation \(\Delta f\).
- Disturbance energy loss:
\[
E_{\mathrm{loss}} = \int_{t_0}^{t_1}\!\big(P_{\mathrm{ref}}(t) – P_{\mathrm{ac}}(t)\big)\,dt
\]
where \(P_{\mathrm{ref}}(t)\) is the nominal target and \(P_{\mathrm{ac}}(t)\) is measured export.
Procedures
| Test | Steps | Recorded Outputs |
|---|---|---|
| Voltage Sags/Swells | Program events (e.g., 50% for 200 ms; 80% for 500 ms). Run sequences per your code profile. | Connection state vs. envelope, \(t_{\mathrm{rec}}\), \(E_{\mathrm{loss}}\), current waveform/THD during event |
| Frequency Deviations | Apply \(\pm\) step or ramp in frequency (e.g., \(\pm 2\ \mathrm{Hz}\)). | Export continuity, PF/VAR response vs. \(\Delta f\), any trips and \(t_{\mathrm{trip}}\) |
| Standardized Profiles | Execute LVRT profiles from applicable standards. | Pass/fail against voltage-time curve, recovery characteristics |
Power Quality Measurement and Compliance Validation
Assess current waveform quality, harmonic emissions, and reactive power behavior to ensure the inverter does not degrade grid power quality and meets applicable limits.
Key Metrics & Calculations
- Total Harmonic Distortion (for voltage or current):
\[
\mathrm{THD} = \frac{\sqrt{\sum_{h=2}^{H} U_h^2}}{U_1}\times 100\%\!,
\]
where \(U_h\) is the RMS of the \(h\)-th harmonic and \(U_1\) is the RMS fundamental (choose \(H\) per standard, e.g., 40). - Power Factor:
\[
\mathrm{PF} = \frac{P}{S} = \frac{V_{\mathrm{rms}} I_{\mathrm{rms}} \cos\phi}{V_{\mathrm{rms}} I_{\mathrm{rms}}} = \cos\phi
\]
(for sinusoidal case; for non-sinusoidal currents, compute \(P/S\) directly from sampled waveforms). - Harmonic Spectrum: individual current harmonics \(I_h\) as percent of \(I_1\) up to the required order.
- Reactive Power Capability \(Q(P)\): measured VARs vs. commanded setpoints at various active power levels.
Procedures
| Test | Steps | Recorded Outputs |
|---|---|---|
| Nominal Condition | Operate at rated power into a clean grid waveform. | THD\(_I\), PF, harmonic spectrum, \(P\), \(Q\) |
| Partial Load Levels | Repeat at 50% and 20% of rated power. | THD\(_I\) vs. load, PF vs. load, harmonic changes |
| Reactive Power Test | Command \(\pm Q\) setpoints (if supported) at several \(P\) levels. | Achieved \(Q\), resultant PF, regulation accuracy |
| Distorted Grid (Optional) | Inject selected harmonics with the simulator. | Inverter contribution to harmonics, immunity/compliance observations |
Traditional Approach to Testing Multiple Micro-Inverters
In a traditional laboratory configuration while it is necessary to test simultaneously multiple units of micro-inverters, each micro-inverter under test is connected to its own dedicated pair of instruments which are programmable DC source as PV simulator on the DC input side and a grid simulator on the AC output side to emulate the overall operation toplogy. While technically straightforward, this setup introduces significant limitations once more than one device must be tested in parallel.

Fig 3, Testing Set-Up for Multiple Units of Micro-Inverters
Setting-up of DC source as PV Simulator Must Match Each Units of Micro-Inverter Correspondingly and Independently
Supposing that in the laboratory the validation and testing of 3 units of micro-inverters is taking place simultaneously. Each of the micro-inverter should have its own input of DC source for purpose that the emulated I-V curve profile for each of them can be independently controllable with user-configured parameters like Voc/Isc/Vmpp/Impp.
If multiple micro-inverters are connected to the same PV I-V curve, each unit’s MPPT algorithm will continuously adjust the operating point and interfere with the others. This “competition” for the single maximum power point causes oscillations, distorted power sharing, and ultimately inaccurate or non-representative test results.
Setting-up of AC Programmable Grid Simulator On the Output Side of the Micro-Inverters
On the AC side, the micro-inverters are connected to a programmable grid simulator that emulates the utility grid.
The simulator provides a stable nominal grid environment (e.g., 230 V/50 Hz or 120 V/60 Hz) and, when required, can introduce controlled disturbances such as voltage sags, frequency deviations, or harmonic distortion. By absorbing and regenerating the power exported from the inverters, the simulator ensures safe operation without feeding energy back into the laboratory supply. This setup allows engineers to validate grid synchronization, ride-through capability, and power quality performance under repeatable and standardized test conditions.
Disadvantges of Traditional Multiple Micro-Inverter Testing Set-Up
Space Requirements due to Multi-Channel Deployment with Multiple Sets of Testing Instruments
Each PV simulator and grid simulator occupies substantial space and requires sufficient clearance for controling and safe cabling. As the number of devices under test increases, the physical footprint of the test setup grows linearly. Testing three or more units can already fill an entire desktop or rack bay, creating congestion in the laboratory, complicating cable routing, and raising challenges for operator access and safety zoning.

Fig 4. Traditional Multi-Channel Testing Takes Considerable Space
Proliferation of Instruments
The traditional approach demands that every micro-inverter has its own PV source and grid source. For three units, this translates to three PV simulators and three grid simulators, plus separate measurement analyzers and protective devices. Scaling to higher counts multiplies the number of instruments, making synchronization and data collection increasingly complex and error-prone.
Instrument Procurement and Total Ownwership Cost
High-precision PV simulators and regenerative grid sources are among the most expensive assets in a power electronics laboratory. Under the traditional approach, capital expenditure scales almost directly with the number of DUTs. Moreover, recurring operational expenses such as calibration, maintenance, and energy consumption also multiply, leading to a significantly higher total cost of ownership.
Operational Inefficiency
Beyond space and cost, setting-up testing environement with multiple sets of instruments also increast operational inefficiencies. Each DUT requires its own protection circuits, wiring, and measurement channels. This raises setup time, increases wiring density, and elevates the risk of configuration errors. Aggregating test data from many independent instruments is cumbersome, slowing throughput and reducing the efficiency of batch testing or long-duration burn-in.
“Helion” Programmable Power Supply Facilitates Testing of Multiple Micro-Inverters
ActionPower’s new series of “HELION” programmable power supplies provide an faciliated and simplified outlet to testing multiple micor-inverters simultaneously while saving instrument cost, reduce space utilization and simplifying wiring and connections.

Fig 5. “Helion” Programmable Power Supply with 6-Channel-Based Architecture Allows Arbitrary Combination and Testing Topology Setup of AC/DC Input/Output
Modular Design Architecture Improves Testing Flexiblity by Replacing Multiple Single-Channel Devices
“Helion” programmable power supply features 6 channels to each of which the users can set up at their discretion AC modules or DC modules and in operation mode as either power source or electronic load. The system identify the modules automatically upon implementation and in a manner of connect to run that faciliate significantly the testing environment setup.

Fig 6. “Helion” Programmable Power Supply Automatically Identify the Module Installed to Each Channel
Multi-Loop Power Cycling Setup with PV Simulation Module and Bidirectional AC Modules
For testing multiple micro-inverters, supposing 3 units of them, users can install to “Helion” programable supply 3 unist of PV simulation modules and 3 units of AC module, with each pair of them connected to the input and output side of micro-inverter. The system then forms a multiple loop architecture with power cycling from DC module to the micro-inverter, then AC electricity converted from the later into AC module which is futher recovered as energy to the DC module (PV simulation module).

Fig 7. Multi-Loop Power Cycling for Testing Multiple Micro-Inverters
Summary
Traditional approach to testing multiple micro-inverters involves connecting to its input and output side a pair of dedicated PV simulator and grid simulator and this method lack scalability when the number of devices to be tested increases, further troubles are with the expanded space requirement, multiplied instrument counts, growing ownership cost, more complex wiring, synchronization and data management complications.
ActionPower’s new release of “Helion” programmable power supply provides an exact-matching solution thanks to its multi-channel and modular-based architecture by which the simultaneous testing for multiple micro-inverters can be simplified to the maximum level that the user will only need one set of instrument instead of, in case of traditional approach, 3 PV simulators and 3 grid simulators.
Learn More
For more information about “Helion” Programmable Multi-Channel Power Supply, you may access the following page:

Zhiwei Bao
Zhiwei Bao holds 20+ patents in the field of mechanical engineering and is keen on industrial automation and product marketing. His interdisciplinary background, along with his passion and initiative for learning, has led him to a profound understanding of power electronics. He manages the technical copywriting for programmable power and testing topics at ActionPower through product-marketing-driven approaches.